Technical Specifications
Function
The CDMX01 converter generates serial signals in a format that
is called DMX512; the output of the lighting controller is connected to a lighting fixture. Each DMX-compatible lighting fixture has a DMX input/output. It is a master-slave system where the lighting controller acts as the master and the lighting fixture as the slave in relation to the controller, but as the master in relation to the next lighting fixture that is connected in a row. The device acts as a DMX master and can control up to 2x 512 DMX slaves. In the Modbus communication topology
the device acts as a slave (server). It receives commands from a Modbus TCP master (client). The typical client is a PLC. The Modbus data is converted to DMX commands for 2 independent DMX channels and sent to the RS485 buses via the DMX512-A protocol. The DMX telegram is sent immediately after writing to the Modbus registers, and optionally on a periodic basis according to the setting of the Modbus register configuration. The period time is configurable in the range of 0.1 to 65.5 s. All parameters and functions of the
converter can be set via the web interface (http protocol) to TCP-
port 80. The device's web pages are used for configuration,
setting the current and default values of the DMX channels, and
for device diagnostics. The web interface and the FTP server can
be disabled at the hardware level (via the USR switch) to
ensure extra security of the device. The Ethernet interface automatically switches between 10 and 100 Mbps.
Design notes
The PLC controls the DMX lights based on data stored in the CDMX01 Modbus registers.
In Sniffer mode, the device does not send data to
DMX, but only reads telegrams from the DMX controller
(master device). The data is stored in the Modbus table.
A Modbus TCP client (master) can read this data from the Modbus table of the converter and process it accordingly. The sniffer mode allows third-party devices connected to the PLC to be controlled via a DMX controller. In this mode, the expected DMX telegram length must be set in the Modbus register (Size).
If the packets are shorter than specified in the Size register,
the converter determines the end of the telegram based on the
start byte of the next telegram, or based on a gap between telegrams that is longer than 1 s.
A DMX channel always operates exclusively in the specified mode.
There may only be one Master device on a DMX bus. The
Master and Sniffer modes can be deliberately combined on
both channels (Master – Master, Sniffer – Sniffer, Master –
Sniffer, Sniffer – Master).
is called DMX512; the output of the lighting controller is connected to a lighting fixture. Each DMX-compatible lighting fixture has a DMX input/output. It is a master-slave system where the lighting controller acts as the master and the lighting fixture as the slave in relation to the controller, but as the master in relation to the next lighting fixture that is connected in a row. The device acts as a DMX master and can control up to 2x 512 DMX slaves. In the Modbus communication topology
the device acts as a slave (server). It receives commands from a Modbus TCP master (client). The typical client is a PLC. The Modbus data is converted to DMX commands for 2 independent DMX channels and sent to the RS485 buses via the DMX512-A protocol. The DMX telegram is sent immediately after writing to the Modbus registers, and optionally on a periodic basis according to the setting of the Modbus register configuration. The period time is configurable in the range of 0.1 to 65.5 s. All parameters and functions of the
converter can be set via the web interface (http protocol) to TCP-
port 80. The device's web pages are used for configuration,
setting the current and default values of the DMX channels, and
for device diagnostics. The web interface and the FTP server can
be disabled at the hardware level (via the USR switch) to
ensure extra security of the device. The Ethernet interface automatically switches between 10 and 100 Mbps.
Design notes
The PLC controls the DMX lights based on data stored in the CDMX01 Modbus registers.
In Sniffer mode, the device does not send data to
DMX, but only reads telegrams from the DMX controller
(master device). The data is stored in the Modbus table.
A Modbus TCP client (master) can read this data from the Modbus table of the converter and process it accordingly. The sniffer mode allows third-party devices connected to the PLC to be controlled via a DMX controller. In this mode, the expected DMX telegram length must be set in the Modbus register (Size).
If the packets are shorter than specified in the Size register,
the converter determines the end of the telegram based on the
start byte of the next telegram, or based on a gap between telegrams that is longer than 1 s.
A DMX channel always operates exclusively in the specified mode.
There may only be one Master device on a DMX bus. The
Master and Sniffer modes can be deliberately combined on
both channels (Master – Master, Sniffer – Sniffer, Master –
Sniffer, Sniffer – Master).